Motor current calculator (three-phase and single-phase)

Estimate the rated current of a motor from its output power, supply voltage, power factor and efficiency. A 4 kW, 400 V three-phase motor draws about 8.1 A.

Inputs

Results

Line current
8.09 A
Apparent power
5.61 kVA
Electrical input power
4.6 kW
Open in simulator with these values →

Formulas

Three-phase motor:

I=P3 U cos⁡φ ηI = \frac{P}{\sqrt{3}\,U\,\cos\varphi\,\eta}

Single-phase motor:

I=PU cos⁡φ ηI = \frac{P}{U\,\cos\varphi\,\eta}

PP is the mechanical output power on the nameplate in W, UU the line voltage in V, cos⁡φ\cos\varphi the power factor and η\eta the efficiency (0 to 1). Losses are why the electrical input is larger than PP; see motor losses and efficiency.

Worked example

A 4 kW three-phase motor on 400 V with cos⁡φ=0.82\cos\varphi = 0.82 and η=0.87\eta = 0.87:

I=40003⋅400⋅0.82⋅0.87≈8.1 AI = \frac{4000}{\sqrt{3} \cdot 400 \cdot 0.82 \cdot 0.87} \approx 8.1\,\mathrm{A}

Practical notes

The current printed on the motor nameplate always wins over a calculated value; use the formula when no nameplate is available. Power factor and efficiency both drop at part load.

In a three-phase system U is the line-to-line voltage. The result is the full-load current, not the starting current. Explore the effect of load in the three-phase induction motor simulator.

Frequently asked questions

How do you calculate the current of a three-phase motor?
I = P / (√3 × U × cos φ × η), with P the output power in W and U the line voltage. 4 kW at 400 V, cos φ 0.82 and η 0.87 gives about 8.1 A.
What is the formula for a single-phase motor?
I = P / (U × cos φ × η), without the √3 factor.
Should I use the input or the output power?
Use the mechanical output power from the nameplate (the kW rating). Efficiency in the formula converts it to input power.
Is this the starting current?
No, it is the full-load running current. Direct-on-line starting current is typically 5 to 8 times higher.