Calculator
Motor current calculator (three-phase and single-phase)
Estimate the rated current of a motor from its output power, supply voltage, power factor and efficiency. A 4 kW, 400 V three-phase motor draws about 8.1 A.
Inputs
Results
- Line current
- 8.09 A
- Apparent power
- 5.61 kVA
- Electrical input power
- 4.6 kW
Formulas
Three-phase motor:
Single-phase motor:
is the mechanical output power on the nameplate in W, the line voltage in V, the power factor and the efficiency (0 to 1). Losses are why the electrical input is larger than ; see motor losses and efficiency.
Worked example
A 4 kW three-phase motor on 400 V with and :
Practical notes
The current printed on the motor nameplate always wins over a calculated value; use the formula when no nameplate is available. Power factor and efficiency both drop at part load.
In a three-phase system U is the line-to-line voltage. The result is the full-load current, not the starting current. Explore the effect of load in the three-phase induction motor simulator.
Frequently asked questions
- How do you calculate the current of a three-phase motor?
- I = P / (√3 × U × cos φ × η), with P the output power in W and U the line voltage. 4 kW at 400 V, cos φ 0.82 and η 0.87 gives about 8.1 A.
- What is the formula for a single-phase motor?
- I = P / (U × cos φ × η), without the √3 factor.
- Should I use the input or the output power?
- Use the mechanical output power from the nameplate (the kW rating). Efficiency in the formula converts it to input power.
- Is this the starting current?
- No, it is the full-load running current. Direct-on-line starting current is typically 5 to 8 times higher.