Transformer turns ratio, voltage and current calculator

For an ideal transformer the voltage ratio equals the turns ratio, and the current ratio is its inverse. Enter the voltage, the turns and the apparent power to get both currents.

Inputs

Results

Turns ratio a = N1 / N2
10
Secondary voltage V2
23 V
Primary current I1
4.35 A
Secondary current I2
43.48 A
Step-down transformer
500 : 50

Ideal transformer: no losses, no leakage, no magnetizing current. Real values differ by a few percent.

Open in simulator with these values →

Formulas

a=N1N2=V1V2=I2I1a = \frac{N_1}{N_2} = \frac{V_1}{V_2} = \frac{I_2}{I_1}
I1=SV1I2=SV2I_1 = \frac{S}{V_1} \qquad I_2 = \frac{S}{V_2}

SS is the apparent power in VA. For a three-phase transformer use I=S/(3 V)I = S / (\sqrt{3}\,V) with line voltages. Background: how a transformer works.

Worked example

A primary of 230 V with 500 turns and a secondary of 50 turns gives a=10a = 10 and V2=230/10=23 VV_2 = 230 / 10 = 23\,\mathrm{V}. For S=0.5 kVAS = 0.5\,\mathrm{kVA}:

I1=500230≈2.17 AI2=50023≈21.7 AI_1 = \frac{500}{230} \approx 2.17\,\mathrm{A} \qquad I_2 = \frac{500}{23} \approx 21.7\,\mathrm{A}

Practical notes

The ideal model ignores winding resistance, leakage flux and core losses, so a real secondary voltage is a few percent lower under load. Never operate a transformer on DC.

Watch it work in the single-phase transformer simulator.

Frequently asked questions

How do you calculate the secondary voltage of a transformer?
V2 = V1 × N2 / N1. With 230 V and a 500:50 turns ratio, V2 = 23 V.
How do you find transformer current from kVA?
I = S / V for single phase, I = S / (√3 × V) for three phase. 0.5 kVA at 230 V is 2.17 A.
What is the turns ratio?
a = N1 / N2, equal to V1 / V2 and to I2 / I1 for an ideal transformer.
Why is the current higher on the low-voltage side?
Power is conserved in an ideal transformer, so V1 I1 = V2 I2: a lower voltage means a proportionally higher current.