Star-delta starting calculator
Star-delta starting cuts the line current and the starting torque to about one third. Enter the supply voltage, rated current and starting current ratio to compare both.
Inputs
Results
- Winding voltage, star
- 230.9 V
- Winding voltage, delta
- 400 V
- Winding current, delta
- 5.77 A
- Starting line current, direct-on-line
- 60 A
- Starting line current, star-delta
- 20 A
- Starting torque, direct-on-line
- 200 % of rated torque
- Starting torque, star-delta
- 67 % of rated torque
Textbook values: star connection divides both the starting current and the starting torque by 3. Real starters add a switching transient.
Open in simulator with these values →Formulas
In star each winding sees the phase voltage, and in delta the phase current is smaller than the line current:
Because the winding voltage in star is of the delta value, the current and torque scale accordingly:
See the star-delta connection guide.
Worked example
A motor on 400 V with and draws when started direct on line. In star the line current is , and the starting torque falls to one third too.
Practical notes
The motor must be rated for delta on your supply, for example 400 V delta / 690 V star on a 400 V network. The low starting torque limits star-delta to light starts such as fans and unloaded pumps; compare other starting methods.
The switch from star to delta causes a short current peak, so change over when the motor has reached about 80 to 90 % of its speed. See the three-phase induction motor simulator.
Frequently asked questions
- How much does star-delta starting reduce the current?
- To one third of the direct-on-line starting current. A motor drawing 49 A direct on line draws about 16.4 A in star.
- What happens to the torque in star?
- The starting torque also falls to about one third, so the load must be light at start.
- What is the relation between line and phase values in delta?
- I_line = √3 × I_phase and the phase voltage equals the line voltage. In star, U_phase = U_line / √3.
- Which motors can be started star-delta?
- Motors with all six winding ends brought out and rated for delta at the supply voltage, such as 400 V delta / 690 V star on a 400 V network.