Star (Y) and delta (Δ) connection of three-phase windings

In a star connection the line voltage is √3 times the phase voltage and line current equals phase current. In a delta connection the line current is √3 times the phase current and line voltage equals phase voltage. Either way the power is P = √3 × V_L × I_L × cos φ, and a 230/400 V motor is wired in delta on a 230 V line and in star on a 400 V line.

Two ways to connect three windings

A three-phase motor, transformer or generator has three identical windings, one per phase. Each winding has two ends, a start and a finish, and they can be joined in two ways.

  • Star (Y, wye): one end of each winding is tied to a common point, the neutral point. The other three ends go to the supply lines L1, L2 and L3.
  • Delta (Δ\Delta): the three windings are joined head to tail in a closed triangle. Each corner of the triangle goes to one supply line.
U₁V₁W₁NYU₁ / W₂V₁ / U₂W₁ / V₂Δ
The same three windings connected in star (left) and delta (right).

The supply line values are called line quantities (VLV_L, ILI_L). The values across and through one winding are called phase quantities (VphV_{\mathrm{ph}}, IphI_{\mathrm{ph}}). The two connections differ in how these relate.

Star connection: V_L = √3 × V_ph

In star, each line is attached to one winding, so the line current is the winding current:

IL=IphI_L = I_{\mathrm{ph}}

The line voltage is measured between two lines, i.e. across two windings in series, whose voltages are 120° apart. Their phasor difference is 3\sqrt{3} times one phase voltage:

VL=3×VphV_L = \sqrt{3} \times V_{\mathrm{ph}}

On a 400 V network each winding therefore sees 400/3≈231 V400 / \sqrt{3} \approx 231\,\mathrm{V}. A star connection also provides a neutral point, which a generator or transformer can bring out as a fourth wire.

Delta connection: I_L = √3 × I_ph

In delta, each winding is connected directly between two lines, so the winding sees the full line voltage:

Vph=VLV_{\mathrm{ph}} = V_L

Each line current splits into two winding currents, 120° apart, and the line current is their phasor difference:

IL=3×IphI_L = \sqrt{3} \times I_{\mathrm{ph}}

On a 400 V network each winding of a delta-connected machine sees 400 V, which is 3\sqrt{3} times more than in star. The same winding at the same line voltage therefore draws 3\sqrt{3} times the phase current and three times the line current and power of the star connection.

Power is the same formula for both

Total power is the sum of three phase powers. In star, 3×Vph×Iph×cos⁡φ3 \times V_{\mathrm{ph}} \times I_{\mathrm{ph}} \times \cos \varphi with Vph=VL/3V_{\mathrm{ph}} = V_L / \sqrt{3} gives

P=3×VL×IL×cos⁡φP = \sqrt{3} \times V_L \times I_L \times \cos \varphi

In delta, 3×Vph×Iph×cos⁡φ3 \times V_{\mathrm{ph}} \times I_{\mathrm{ph}} \times \cos \varphi with Iph=IL/3I_{\mathrm{ph}} = I_L / \sqrt{3} gives exactly the same expression. This is why the nameplate and the power formula always use line values, whatever the connection.

The angle φ\varphi is the phase angle between a phase voltage and the current in the same phase, and cos⁡φ\cos \varphi is the power factor.

The terminal box and the 230/400 V nameplate

A standard motor brings both ends of each winding to the terminal box: U1, V1, W1 are the starts and U2, V2, W2 are the finishes. They are arranged in two rows, with U1, V1, W1 under W2, U2, V2.

  • Star: three links join U2, V2 and W2 together. The supply goes to U1, V1 and W1.
  • Delta: three links join the terminals one above the other (U1 with W2, V1 with U2, W1 with V2). The supply goes to the three link points.

The nameplate says which connection suits which supply, for example Δ/Y\Delta/Y 230/400 V. Each winding is designed for 230 V. On a 230 V line-to-line supply you use delta, and on a 400 V line-to-line supply you use star. In both cases the winding sees 230 V, so the motor produces the same torque, speed and power. A motor plate marked 400/690 V Δ/Y\Delta/Y follows the same rule for 400 V and 690 V networks.

Connecting a 230/400 V motor in delta on 400 V puts 400 V across windings designed for 230 V. The current rises sharply and the winding overheats.

Worked example

A 4 kW motor is marked Δ/Y\Delta/Y 230/400 V, 8.2 A at 400 V, cos⁡φ=0.82\cos \varphi = 0.82, and runs on a 400 V network, so it is wired in star.

1. Winding voltage: Vph=400/3≈231 VV_{\mathrm{ph}} = 400 / \sqrt{3} \approx 231\,\mathrm{V}. 2. Winding current: Iph=IL=8.2I_{\mathrm{ph}} = I_L = 8.2 A. 3. Input power: P=3×400×8.2×0.82≈4.66 kWP = \sqrt{3} \times 400 \times 8.2 \times 0.82 \approx 4.66\,\mathrm{kW}. With 4 kW at the shaft, the efficiency is about 86%.

Now the same motor on a 230 V network, wired in delta. Each winding still sees 230 V and carries 8.2 A, so the line current is

IL=3×Iph=1.732×8.2≈14.2I_L = \sqrt{3} \times I_{\mathrm{ph}} = 1.732 \times 8.2 \approx 14.2 A

and P=3×230×14.2×0.82≈4.64 kWP = \sqrt{3} \times 230 \times 14.2 \times 0.82 \approx 4.64\,\mathrm{kW}, the same within rounding. The lower voltage requires more line current for the same power.

Finally, star-delta starting. Take a motor marked Δ/Y\Delta/Y 400/690 V on a 400 V network. It runs in delta, with 400 V across each winding. For starting, the windings are first connected in star, so each gets 400/3≈231 V400 / \sqrt{3} \approx 231\,\mathrm{V}, which is 1/31/\sqrt{3} of the running voltage. The phase current falls by 1/31/\sqrt{3}, and because the star line current equals the phase current, the line current is 1/3×1/3=1/31/\sqrt{3} \times 1/\sqrt{3} = 1/3 of the direct-on-line value. Torque follows the square of the winding voltage, so it also falls to 1/3.

Try it in the three-phase induction motor simulator

The simulator does not have a switch for the terminal box connection; the motor is described by its line values. It does, however, model the star-delta connection in the starting method. Open the three-phase induction motor simulator and keep the default 4 kW, 400 V, 8.2 A, four-pole motor.

  • Under Starting method, choose Direct on line (DOL) and note the Peak starting current ×In\times I_n and Start time readouts.
  • Switch to Star-delta. The simulator applies 1/31/\sqrt{3} of the voltage until the switch-over time (default 3 s, set by Switch-over time to full voltage) and then full voltage. The chart marks the change with a Y→Δ label.
  • Compare the Peak starting current ×In\times I_n of the two runs. During the star stage the line current is about one third of the direct start; the peak after the switch-over to delta can be higher than that, so compare the readout with the shape of the current curve.
  • Raise Mechanical load while in star-delta. With only a third of the torque available during the star stage, expect a longer Start time under a heavy load.

The wound-rotor induction motor simulator has the same Starting method control. The 3D motor model includes a terminal box cover, but the star and delta links themselves are not modelled.

Sources and further reading

  • S. J. Chapman, "Electric Machinery Fundamentals", McGraw-Hill.
  • IEC 60034-8, "Rotating electrical machines: Terminal markings and direction of rotation".
  • IEC 60034-12, "Rotating electrical machines: Starting performance of single-speed three-phase cage induction motors".

Try it in the simulator

Frequently asked questions

How do you convert between star and delta?
For identical impedances, a delta network is equivalent to a star network with one third of the impedance: ZY=ZΔ/3Z_Y = Z_\Delta / 3. For machines, the key relations are VL=3×VphV_L = \sqrt{3} \times V_{\mathrm{ph}} in star and IL=3×IphI_L = \sqrt{3} \times I_{\mathrm{ph}} in delta.
What does 230/400 V Δ/Y on a nameplate mean?
Each winding is rated for 230 V. Connect it in delta on a 230 V line-to-line supply and in star on a 400 V line-to-line supply. The winding voltage is 230 V in both cases.
Which connection draws more current from the line?
At the same line voltage and the same windings, delta draws three times the line current and three times the power of star. That is why star-delta starting reduces the inrush.
Why does the power formula use √3?
Because phase quantities are 120° apart. In star the line voltage is the phasor difference of two phase voltages and in delta the line current is the difference of two phase currents, and both give a factor 3\sqrt{3}. The result P=3×VL×IL×cos⁡φP = \sqrt{3} \times V_L \times I_L \times \cos \varphi is valid for either connection.
What happens if a motor is connected in delta by mistake on the higher voltage?
A 230/400 V motor in delta on 400 V has 400 V across windings designed for 230 V. The magnetic circuit saturates, the current rises sharply and the motor overheats quickly. Always check the plate and the supply.