Induction motor slip: formula, calculation and examples
Slip is the difference between the rotating magnetic field's synchronous speed and the rotor speed, as a fraction of synchronous speed: s = (N_s − N) / N_s, with N_s = 120 × f / p. A 50 Hz four-pole motor has N_s = 1500 rpm, and a rotor turning at 1440 rpm has a slip of 4%.
Synchronous speed
The stator windings of a three-phase motor create a magnetic field that rotates at the synchronous speed
where is the supply frequency in hertz and is the number of poles. The result is in revolutions per minute.
- 2 poles at 50 Hz: 3000 rpm
- 4 poles at 50 Hz: 1500 rpm
- 4 poles at 60 Hz: 1800 rpm
- 6 poles at 50 Hz: 1000 rpm
The rotor of an induction motor never reaches this speed while producing torque, which is why the motor is also called asynchronous.
What slip is and why it exists
Slip, , measures how far the rotor lags the field. It is often quoted as a percentage.
The lag is essential. Torque comes from currents induced in the rotor bars, and currents are induced only when the rotor conductors move relative to the field. If the rotor ran exactly at , there would be no relative motion, no induced current and no torque. As the load increases, the rotor slows slightly, the relative motion grows, more current is induced and more torque is produced.
At standstill (100%), and at synchronous speed . The frequency of the rotor currents is , which is why it is small at normal operating speeds, for example 2 Hz on a 50 Hz motor with 4% slip.
Worked example
Take a 4 kW, 400 V, four-pole motor on a 50 Hz supply with a nameplate speed of 1440 rpm. This is the default motor in the induction motor simulator.
1. Synchronous speed: . 2. Rated slip: , or 4%. 3. Shaft torque at rated output: .
If the supply frequency changes, the synchronous speed changes in proportion. At 60 Hz the same four-pole motor has , and the same 4% slip gives 1728 rpm.
The torque–speed curve
The torque–speed curve of an induction motor has a characteristic shape. At standstill, the motor produces its starting torque. As speed rises, torque increases to a maximum, called the pull-out or breakdown torque, then falls to zero at synchronous speed.
Near synchronous speed, torque is roughly proportional to slip, so the curve is close to a straight line. This is the stable operating region, and a loaded motor runs in it, a few percent below . Beyond the pull-out point, torque falls as slip grows, so a motor loaded past that point slows down further and stalls.
Torque also varies roughly with the square of the supply voltage. A drop to 80% voltage cuts the torque available at any speed to about 64%, which matters at start-up and under heavy load.
Curvo Studio's three-phase induction motor simulator plots this curve in its Torque-speed curve chart: the Motor torque curve, the Load torque curve, the Operating point where they cross, and the Breakdown torque. The motor stays stable where the load curve crosses the motor curve on the steep part near synchronous speed, and stalls when the load torque is above the breakdown torque.
The curve gets its own guide: the induction motor torque–speed curve covers the starting, pull-out and rated points and the equations behind them.
How the simulator models load and slip
The simulator is a steady-state lesson model, not a manufacturer datasheet. From the nameplate it fits a per-phase equivalent circuit (stator and rotor resistance, leakage reactances, a magnetizing branch and an iron-loss resistance) so that rated load gives the nameplate speed and current, with a breakdown torque of about 3.1 times rated torque.
- The Mechanical load setting is a percentage of rated torque ( at the nameplate speed). It is applied through the selected load type: No load (free shaft, friction and windage only), Constant torque, Fan / pump, Constant power or Linear (viscous). The Mechanical load slider is disabled while No load is selected.
- The motor torque is calculated from the circuit across the whole slip range. The operating point is where it meets the load torque plus a small friction torque, and slip, speed, current, Efficiency and Power factor follow from the circuit at that slip.
- Torque scales roughly with the square of the voltage, so the Breakdown torque falls with the Applied line voltage. Reactances follow the supply frequency.
- If the load torque is above the breakdown torque, or the starting torque cannot overcome the load at standstill, the motor is flagged Stalled: slip is shown as 100%, the speed is zero and the current is the locked-rotor current.
For the default 4 kW motor at 400 V and 50 Hz, the breakdown torque is about 82 N·m, roughly 3.1 times the rated 26.5 N·m. The starting torque is about 55 N·m and the locked-rotor current about 48 A, close to six times the rated 8.2 A.
Try it in the induction motor simulator
Open the three-phase induction motor simulator and keep the default 4 kW, 400 V, four-pole, 50 Hz motor. Under Load type, choose Constant torque, because the Mechanical load slider is disabled for No load.
- Set the Mechanical load to 0%, 25%, 50%, 75% and 100% and note the rotor speed. You should read about 1499, 1486, 1471, 1456 and 1440 rpm (the last is the nameplate speed). Slip rises almost in a straight line with load, from 0.05% to 4.0%.
- Raise the load to its 120% limit: the speed is about 1426 rpm (slip 4.9%) and the current about 9.5 A. At rated voltage the motor does not stall, because the Torque-speed curve chart shows the operating point still well below the Breakdown torque.
- Return to 65% load and reduce the Applied line voltage to 320 V (80%). Slip rises from about 2.5% to 4.1% (1438 rpm), and the Breakdown torque on the chart falls from about 82 N·m to 53 N·m.
- Keep lowering the voltage. At 65% load the motor stalls at about 220 V, and at 100% load at about 270 V. The speed drops to 0 and the current jumps to the locked-rotor value, roughly 26 to 32 A.
- Set the Supply frequency to 60 Hz and see the Synchronous speed move to 1800 rpm. The voltage stays at 400 V, so the flux is reduced and slip at 65% load is about 3.1% (1745 rpm). Raising the voltage to 480 V keeps the V/f ratio and gives about 1763 rpm.
The voltage experiments show the same lesson: slip is the price of torque, and lower voltage means more slip for the same load.
Sources and further reading
- S. J. Chapman, "Electric Machinery Fundamentals", McGraw-Hill.
- IEEE Std 112, "Standard Test Procedure for Polyphase Induction Motors and Generators".
- IEC 60034-1, "Rotating electrical machines: Rating and performance".
Try it in the simulator
Frequently asked questions
- What is slip in an induction motor?
- Slip is the fractional difference between synchronous speed and rotor speed: . It is zero at synchronous speed and 1 (100%) at standstill.
- How do you calculate synchronous speed?
- , with the supply frequency in hertz and the number of poles. A four-pole motor on 50 Hz has a synchronous speed of 1500 rpm.
- Why does an induction motor need slip?
- Torque comes from currents induced in the rotor, and these exist only if the rotor moves relative to the rotating field. At zero slip there is no induced current and no torque.
- What happens to slip when the load increases?
- Slip increases, so the rotor slows slightly while producing more torque. If the load exceeds the pull-out torque, the motor stalls.
- Does the Curvo Studio simulator plot the torque–speed curve?
- Yes. The Torque-speed curve chart shows the Motor torque and Load torque curves, the Operating point and the Breakdown torque. A Performance vs. load chart plots current, slip, efficiency and power factor against load, and the motor is flagged Stalled when the load is too high for the voltage.